← Voltar ao feed

Midnight Blue finds six unpatched pre-auth RCE zero-days in Danfoss AK-SM800A refrigeration controllers (≤5.3.2)

1 fonte(s) · 1 atualização(ões) · publicado 17/11/2026 11:41 · coletado há 3 horas

Researcher Carlo Meijer of Midnight Blue found six pre-authentication stack-based buffer overflows in the Danfoss AK-SM800A refrigeration controller. He found them in under an hour of manual firmware review. All firmware up to and including 5.3.2 is affected. No CVE IDs have been assigned because coordinated disclosure with Danfoss is still running. No patch exists, and the researchers say version 5.4.0 does not fix the flaws. Neither Germany's BSI nor the researchers link the flaws to the autumn 2026 attacks on Danfoss and Copeland controllers in Europe, and BSI is not aware of in-the-wild exploitation. This report is based on the article alone. No web research was done, so there is no vendor advisory, CVSS score or fix information.

Entenda a falha

A vulnerabilidade

Midnight Blue's Carlo Meijer found six stack-based buffer overflows in the Danfoss AK-SM800A refrigeration controller. Five are in unauthenticated web request handlers of the sm_app binary and one is in sm_fcgi_app, the gateway that enforces Strict mode. An attacker with network reach to the web interface needs no login. Code execution would give root, and the controllers have no secure boot. All firmware up to and including 5.3.2 is affected. No fix exists, and the researchers say 5.4.0 is not fixed either. No CVE IDs have been assigned yet.

Como funciona

A request reaches the controller's web services, where sm_app handlers copy request data into fixed-size stack buffers using strcpy. Nothing checks the length of the input first. Oversized input therefore overruns the buffer and overwrites adjacent stack memory. In the sixth case, Strict mode (default since 4.0, requiring HTTPS and session tokens) normally blocks most unauthenticated traffic. But the flaw is in sm_fcgi_app, the component that enforces it. In an emulator this crashed the service, and the researchers say it could become code execution.

Por que é vulnerável

The root cause is unsafe memory handling: sm_app uses hundreds of unchecked strcpy calls. The binary is also built without stack canaries or PIE and runs as root, so an overflow is easy to exploit and the impact is maximal. The researchers note that strcpy stopping at null bytes is the only real hurdle, and they say it is not hard to overcome. The device also lacks secure boot, which lets malicious code persist. Midnight Blue criticizes Danfoss's IEC 62443-4-1 secure-development certification, saying the compiler flags contradict it.

Onde está

The articles name the sm_app binary (unauthenticated web request handlers) and the sm_fcgi_app gateway, but no specific functions, files or commits, and no public advisory exists yet.

Como foi descoberta

Carlo Meijer of Midnight Blue found the flaws in under an hour of casual manual review of firmware that anyone can download from Danfoss's site. The work followed attacks since 11 October on Danfoss and Copeland controllers in Europe. Neither the researchers nor the agencies link the six flaws to those attacks, and Germany's BSI knows of no in-the-wild exploitation. Coordinated disclosure with Danfoss is still ongoing, which is why there are no CVEs. Earlier AK-SM800A bugs were documented in 2023 and 2025. On 5.4.0, BSI first said it was not affected and then said it cannot rule that out, while Midnight Blue says it is not fixed.

PoC existente, privada

O exploit existe, mas quem o tem não o publicou.

The researchers reproduced a crash of the sixth flaw in an emulator with Strict mode on, and they say it could become code execution with more work. They say they will not share their exploitation approach for now, and no article shows a published exploit for these six flaws. Public exploits did appear for earlier AK-SM800A bugs within 48 hours of the French attacks, so exploitation of this class is plausibly quick. Exposure should be reduced now rather than waiting for a patch.

Explicação gerada por IA a partir da matéria e dos artigos, em 17/11/2026 13:15.

Detalhes técnicos

  • Five flaws sit in unauthenticated web request handlers of sm_app. This large binary uses hundreds of unchecked strcpy calls, has no stack canaries or PIE, and runs as root.
  • The sixth flaw is in sm_fcgi_app, the gateway that enforces Strict mode. Strict mode has been the default since version 4.0 and requires HTTPS and session tokens. In an emulator the flaw crashed the service, and the researchers say it could become code execution with more work.
  • The controllers have no secure boot. A root attacker could change settings, trigger defrost cycles, hide activity from logs, plant malware that survives factory reset and firmware updates, or wipe the flash and brick the device.

Remediação

  • Restrict management interfaces to a VPN, a private APN or a strict firewall IP whitelist. Geofencing and blacklists are not sufficient.
  • Inventory every internet-exposed controller, including those behind integrator 4G modems.
  • Check settings for unauthorized changes: temperatures, defrost schedules, alarms, accounts and remote access.
  • If compromise is suspected, change all passwords.
  • Do not cut off service providers. Review contracts and insurance first, then set up secure remote access.

Relatos divergentes

BSI first said 5.4.0 was not affected, then corrected itself and said it cannot rule that out. Midnight Blue says 5.4.0 is not fixed.

Linha do tempo

  1. securityaffairs.com ↗ · pub. 17/11/2026 11:41 · coletado 17/11 13:00 primeiro registro

    Midnight Blue finds six unpatched pre-auth RCE zero-days in Danfoss AK-SM800A refrigeration controllers (≤5.3.2)

    ler a análise desta fonte

    Researcher Carlo Meijer of Midnight Blue found six pre-authentication stack-based buffer overflows in the Danfoss AK-SM800A refrigeration controller. He found them in under an hour of manual firmware review. All firmware up to and including 5.3.2 is affected. No CVE IDs have been assigned because coordinated disclosure with Danfoss is still running. No patch exists, and the researchers say version 5.4.0 does not fix the flaws. Neither Germany's BSI nor the researchers link the flaws to the autumn 2026 attacks on Danfoss and Copeland controllers in Europe, and BSI is not aware of in-the-wild exploitation. This report is based on the article alone. No web research was done, so there is no vendor advisory, CVSS score or fix information.

    Technical Details

    • Five flaws sit in unauthenticated web request handlers of sm_app. This large binary uses hundreds of unchecked strcpy calls, has no stack canaries or PIE, and runs as root.
    • The sixth flaw is in sm_fcgi_app, the gateway that enforces Strict mode. Strict mode has been the default since version 4.0 and requires HTTPS and session tokens. In an emulator the flaw crashed the service, and the researchers say it could become code execution with more work.
    • The controllers have no secure boot. A root attacker could change settings, trigger defrost cycles, hide activity from logs, plant malware that survives factory reset and firmware updates, or wipe the flash and brick the device.

    Remediation

    • Restrict management interfaces to a VPN, a private APN or a strict firewall IP whitelist. Geofencing and blacklists are not sufficient.
    • Inventory every internet-exposed controller, including those behind integrator 4G modems.
    • Check settings for unauthorized changes: temperatures, defrost schedules, alarms, accounts and remote access.
    • If compromise is suspected, change all passwords.
    • Do not cut off service providers. Review contracts and insurance first, then set up secure remote access.

    Conflicting Reports

    BSI first said 5.4.0 was not affected, then corrected itself and said it cannot rule that out. Midnight Blue says 5.4.0 is not fixed.